Fire Alarm centers

Detail

Price : Contact

Status : Stocking

Category : Fire alarm

- Power Supply: 230VAC (+ 10%, -15%)
- DC Power supply norms: 24V 3 Amps
- Fuse protection: 250V 1,6Amp
- Shell material: neutral steel 1.2 mm
- Maximum battery capacity: 7Ah-12Vdc (2 batteries for each cabinet)

- Next point error output: 30VDC 1 Amp
- Next alarm fire alarm point output: 30VDC 1 Amp
- The number of smoke detectors mounted on a channel: 25 pieces (SLV-24N)
- Bell output current: 0,5A per head (1,6A on all outputs)
- Current monitoring channel input: 1,6mA
- Resistor End of Line control channel: 6,8K
- Resistor End of Line control the bell, speaker: 10K
- Usually the biggest cable wiring problems were to rebel: 2,5mm2
- Working environment temperature: -5 ° C ~ + 50 ° C
- Humidity: 95% non-condensing

Back Home

Other Product

COUPLING LIVA Lightning rod.
Exit light Kentom
Emergency Lamp Kentom
Angle Valve Fire
Sri fire extinguishers - Malaysia
Call: 0901586114 - 0914811976